Technical specifications
Built-in depth
69mm
Number of poles (total)
2
Release characteristic
D
Rated voltage
415V
Number of protected poles
2
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
-kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Rated insulation voltage Ui
500V
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
25kA
Rated impulse withstand voltage Uimp
6kV
Voltage type
Other
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
100kA
Frequency
50 - 60Hz
Rated current
1A
Power loss
2.6W
Current limiting class
-
Width in number of modular spacings
2.0
Over voltage category
4
Flush-mounted installation
No
Concurrently switching neutral conductor
No
Ambient temperature during operating
-40 - 70°C
Pollution degree
3
Additional equipment possible
Yes
Connectable conductor cross section multi-wired
0.75 - 25mm²
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
0.75 - 35mm²
Explosion-proof
No
From same serie
2CDS382001R0011 | S302P-D1

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Built-in depth
69mm
Number of poles (total)
2
Release characteristic
D
Rated voltage
415V
Number of protected poles
2
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
-kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Rated insulation voltage Ui
500V
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
25kA
Rated impulse withstand voltage Uimp
6kV
Voltage type
Other
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
100kA
Frequency
50 .. 60Hz
Rated current
1A
Power loss
2.6W
Current limiting class
-
Width in number of modular spacings
2.0
Over voltage category
4
Flush-mounted installation
Concurrently switching neutral conductor
Ambient temperature during operating
-40 .. 70°C
Pollution degree
3
Additional equipment possible
Connectable conductor cross section multi-wired
0.75 .. 25mm²
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
0.75 .. 35mm²
Explosion-proof
From same serie