Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
2500A
Overload release current setting
1000.0 - 2500A
Rated voltage
900 - 900V
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Integrated earth fault protection
No
With switched-off indicator
Yes
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
With under voltage release
No
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Type of control element
Push button
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA104496R1 | E2.2H/E9 2500 Ekip Touch LSI 4p WMP 900V

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
2500A
Overload release current setting
1000.0 .. 2500A
Rated voltage
900 .. 900V
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Integrated earth fault protection
With switched-off indicator
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
With under voltage release
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Type of control element
Push button
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
From same serie