Aleta.hr
Main Product Image

1SDA079134R1 | E6.2V-A 4000 Ekip G Touch LSIG 3p WMP

Code: 1985487

ManufacturerRAZNO
Catalog number1SDA079134R1
Type
EAN code8015644855574

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

4000A

Rated voltage

600 - 600V

Adjustment range short-term delayed short-circuit release

2400.0 - 40000A

Overload release current setting

1600.0 - 4000A

Adjustment range undelayed short-circuit release

6000.0 - 60000A

Type of electrical connection of main circuit

Connection at separate chassis part

Integrated earth fault protection

Yes

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

DIN rail (top hat rail) mounting optional

No

Number of auxiliary contacts as normally closed contact

0

Device construction

Built-in device slide-in technique (withdrawable)

With switched-off indicator

Yes

Suitable for DIN rail (top hat rail) mounting

No

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Complete device with protection unit

Yes

Motor drive integrated

No

Motor drive optional

Yes

Degree of protection (IP)

IP30


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA079134R1 | E6.2V-A 4000 Ekip G Touch LSIG 3p WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

4000A

Rated voltage

600 .. 600V

Adjustment range short-term delayed short-circuit release

2400.0 .. 40000A

Overload release current setting

1600.0 .. 4000A

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

Type of electrical connection of main circuit

Connection at separate chassis part

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Device construction

Built-in device slide-in technique (withdrawable)

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Complete device with protection unit

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30