Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
600 - 600V
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Overload release current setting
1600.0 - 4000A
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
With switched-off indicator
Yes
With under voltage release
No
Motor drive integrated
No
Type of control element
Push button
Position of connection for main current circuit
Back side
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Rated permanent current Iu
4000A
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Motor drive optional
Yes
From same serie
1SDA078893R1 | E6.2V-A 4000 Ekip Touch LSIG 3p F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
600 .. 600V
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Overload release current setting
1600.0 .. 4000A
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
With switched-off indicator
With under voltage release
Motor drive integrated
Type of control element
Push button
Position of connection for main current circuit
Back side
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Complete device with protection unit
Rated permanent current Iu
4000A
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
6000.0 .. 60000A