

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
1600.0 - 4000A
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
6000.0 - 60000A
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
No
Rated voltage
600 - 600V
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Yes
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Yes
Number of poles
3
Motor drive integrated
No
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078832R1 | E6.2H-A 4000 Ekip Touch LSI 3p F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
1600.0 .. 4000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
With switched-off indicator
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Rated voltage
600 .. 600V
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Number of poles
3
Motor drive integrated
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
From same serie
We use cookies to enhance your experience.