Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
3200A
With switched-off indicator
Yes
Rated voltage
600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Overload release current setting
1280.0 - 3200A
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078767R1 | E4.2V-A 3200 Ekip G Hi-Touch LSIG 4p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
3200A
With switched-off indicator
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Overload release current setting
1280.0 .. 3200A
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4