

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1280.0 - 3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Rated voltage
600 - 600V
Integrated earth fault protection
Yes
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Complete device with protection unit
Yes
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078760R1 | E4.2V-A 3200 Ekip Dip LSIG 4p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1280.0 .. 3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated voltage
600 .. 600V
Integrated earth fault protection
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
With switched-off indicator
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive optional
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
From same serie
We use cookies to enhance your experience.