Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated permanent current Iu
1600A
Rated voltage
600 - 600V
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Number of poles
3
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078507R1 | E4.2V-A 1600 Ekip G Hi-Touch LSIG 3p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated permanent current Iu
1600A
Rated voltage
600 .. 600V
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Number of poles
3
Complete device with protection unit
Degree of protection (IP)
IP30
From same serie