Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Overload release current setting
1280.0 - 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Rated voltage
600 - 600V
Device construction
Built-in device slide-in technique (withdrawable)
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive integrated
No
Motor drive optional
Yes
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078470R1 | E4.2S-A 3200 Ekip Dip LSIG 3p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Overload release current setting
1280.0 .. 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Rated voltage
600 .. 600V
Device construction
Built-in device slide-in technique (withdrawable)
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
Motor drive optional
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of poles
3