Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
1280.0 - 3200A
Rated voltage
600 - 600V
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Motor drive integrated
No
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078379R1 | E4.2H-A 3200 Ekip Dip LSI 3p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
1280.0 .. 3200A
Rated voltage
600 .. 600V
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Motor drive integrated
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Motor drive optional
Number of auxiliary contacts as change-over contact
4