Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2500A
Overload release current setting
1000.0 - 2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
600 - 600V
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Degree of protection (IP)
IP30
Integrated earth fault protection
Yes
Motor drive integrated
No
With switched-off indicator
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA078144R1 | E4.2H-A 2500 Ekip G Touch LSIG 4p F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2500A
Overload release current setting
1000.0 .. 2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
600 .. 600V
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Motor drive optional
Position of connection for main current circuit
Back side
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Degree of protection (IP)
IP30
Integrated earth fault protection
Motor drive integrated
With switched-off indicator
From same serie