Aleta.hr
Aleta.hr
Main Product Image

1SDA078057R1 | E4.2V-A 2000 Ekip G Hi-Touch LSIG 3p F HR

Code: 1985080

ManufacturerRAZNO
Catalog number1SDA078057R1
Type
EAN code8015644844806

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

2000A

Adjustment range undelayed short-circuit release

3000.0 - 30000A

Rated voltage

600 - 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Integrated earth fault protection

Yes

Adjustment range short-term delayed short-circuit release

1200.0 - 20000A

Suitable for DIN rail (top hat rail) mounting

No

Overload release current setting

800.0 - 2000A

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Yes

DIN rail (top hat rail) mounting optional

No

Number of poles

3

Degree of protection (IP)

IP30

Motor drive optional

Yes

Motor drive integrated

No

With under voltage release

No

Complete device with protection unit

Yes

Position of connection for main current circuit

Back side

Device construction

Built-in device fixed built-in technique

Type of control element

Push button


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

Code: 1985080

1SDA078057R1 | E4.2V-A 2000 Ekip G Hi-Touch LSIG 3p F HR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

2000A

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Suitable for DIN rail (top hat rail) mounting

Overload release current setting

800.0 .. 2000A

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

DIN rail (top hat rail) mounting optional

Number of poles

3

Degree of protection (IP)

IP30

Motor drive optional

Motor drive integrated

With under voltage release

Complete device with protection unit

Position of connection for main current circuit

Back side

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

From same serie