Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800 A
With integrated under voltage release
No
Rated voltage
600 - 600V
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
320.0 - 800A
Motor drive optional
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
Yes
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Motor drive integrated
No
Number of poles
3
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA077583R1 | E2.2H-A 800 Ekip Touch LSIG 3p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800 A
With integrated under voltage release
Rated voltage
600 .. 600V
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
320.0 .. 800A
Motor drive optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Motor drive integrated
Number of poles
3
From same serie