Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1200A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1800.0 - 18000A
With switched-off indicator
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Number of poles
4
With under voltage release
No
Position of connection for main current circuit
Back side
Motor drive integrated
No
Complete device with protection unit
Yes
Overload release current setting
480.0 - 1200A
Motor drive optional
Yes
Type of control element
Push button
Rated voltage
600 - 600V
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
720.0 - 12000A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA077424R1 | E2.2H-A 1200 Ekip G Touch LSIG 4p F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1200A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1800.0 .. 18000A
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Number of poles
4
With under voltage release
Position of connection for main current circuit
Back side
Motor drive integrated
Complete device with protection unit
Overload release current setting
480.0 .. 1200A
Motor drive optional
Type of control element
Push button
Rated voltage
600 .. 600V
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
720.0 .. 12000A
From same serie
We use cookies to enhance your experience.