Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
800A
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Motor drive integrated
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
600 - 600V
Overload release current setting
320.0 - 800A
With under voltage release
No
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
Type of control element
Push button
Number of poles
3
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA077362R1 | E2.2V-A 800 Ekip Touch LSI 3p F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
800A
Motor drive optional
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Motor drive integrated
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
600 .. 600V
Overload release current setting
320.0 .. 800A
With under voltage release
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Position of connection for main current circuit
Back side
Type of control element
Push button
Number of poles
3
From same serie