Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Overload release current setting
640.0 - 1600A
Degree of protection (IP)
IP30
Number of poles
3
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Rated voltage
600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA077327R1 | E2.2S-A 1600 Ekip G Hi-Touch LSIG 3p F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Overload release current setting
640.0 .. 1600A
Degree of protection (IP)
IP30
Number of poles
3
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Complete device with protection unit
Motor drive optional
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
From same serie