Aleta.hr
Main Product Image

1SDA077263R1 | E2.2H-A 1600 Ekip Touch LSIG 3p F HR

Code: 1984366

ManufacturerRAZNO
Catalog number1SDA077263R1
Type
EAN code8015644836863

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated voltage

600 - 600V

Adjustment range undelayed short-circuit release

2400.0 - 24000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Adjustment range short-term delayed short-circuit release

960.0 - 16000A

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

No

Integrated earth fault protection

Yes

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

1600A

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Yes

DIN rail (top hat rail) mounting optional

No

Overload release current setting

640.0 - 1600A

Type of control element

Push button

Position of connection for main current circuit

Back side

Number of poles

3

Motor drive integrated

No

Complete device with protection unit

Yes

Degree of protection (IP)

IP30

Motor drive optional

Yes


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA077263R1 | E2.2H-A 1600 Ekip Touch LSIG 3p F HR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated voltage

600 .. 600V

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

1600A

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

DIN rail (top hat rail) mounting optional

Overload release current setting

640.0 .. 1600A

Type of control element

Push button

Position of connection for main current circuit

Back side

Number of poles

3

Motor drive integrated

Complete device with protection unit

Degree of protection (IP)

IP30

Motor drive optional

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

We use cookies to enhance your experience.