Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1200A
Overload release current setting
480.0 - 1200A
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
600 - 600V
With under voltage release
No
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Integrated earth fault protection
Yes
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
720.0 - 12000A
Adjustment range undelayed short-circuit release
1800.0 - 18000A
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA077224R1 | E1.2S-A 1200 Ekip G Touch LSIG 4p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1200A
Overload release current setting
480.0 .. 1200A
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
600 .. 600V
With under voltage release
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Integrated earth fault protection
With switched-off indicator
DIN rail (top hat rail) mounting optional
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Motor drive integrated
Adjustment range short-term delayed short-circuit release
720.0 .. 12000A
Adjustment range undelayed short-circuit release
1800.0 .. 18000A
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Degree of protection (IP)
IP30
From same serie