Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800 A
With integrated under voltage release
No
Rated voltage
600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Overload release current setting
320.0 - 800A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
With switched-off indicator
Yes
Integrated earth fault protection
Yes
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Degree of protection (IP)
IP30
Motor drive integrated
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA077137R1 | E1.2S-A 800 Ekip G Hi-Touch LSIG 3p WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800 A
With integrated under voltage release
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Overload release current setting
320.0 .. 800A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
With switched-off indicator
Integrated earth fault protection
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Degree of protection (IP)
IP30
Motor drive integrated
Complete device with protection unit
Motor drive optional
Number of auxiliary contacts as change-over contact
4
From same serie