Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800 A
With integrated under voltage release
No
Rated voltage
600 - 600V
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Overload release current setting
320.0 - 800A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of poles
3
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Type of control element
Push button
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA076972R1 | E1.2S-A 800 Ekip Touch LSI 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800 A
With integrated under voltage release
Rated voltage
600 .. 600V
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Overload release current setting
320.0 .. 800A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of poles
3
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Type of control element
Push button
From same serie