Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
250 A
With integrated under voltage release
No
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
375.0 - 3750A
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Rated voltage
600 - 600V
Overload release current setting
100.0 - 250A
Complete device with protection unit
Yes
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive optional
Yes
Adjustment range short-term delayed short-circuit release
150.0 - 2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA076955R1 | E1.2S-A 250 Ekip Hi-Touch LSI 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
250 A
With integrated under voltage release
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
375.0 .. 3750A
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Rated voltage
600 .. 600V
Overload release current setting
100.0 .. 250A
Complete device with protection unit
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive optional
Adjustment range short-term delayed short-circuit release
150.0 .. 2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
From same serie