Aleta.hr
Main Product Image

1SDA075478R1 | XT4N 250 Ekip LSIG In=40A 3p F F UL/CSA

Code: 1983720

ManufacturerRAZNO
Catalog number1SDA075478R1
Type
EAN code8015644794552

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Rated permanent current Iu

250A

Overload release current setting

16.0 - 40A

Adjustment range short-term delayed short-circuit release

40 - 400A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

25kA

Integrated earth fault protection

Yes

Adjustment range undelayed short-circuit release

40 - 400A

Device construction

Built-in device fixed built-in technique

Rated voltage

240 - 600V

Suitable for DIN rail (top hat rail) mounting

No

DIN rail (top hat rail) mounting optional

Yes

With under voltage release

No

Number of poles

3

Position of connection for main current circuit

Front side

Motor drive integrated

No

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

No

Motor drive optional

Yes

Type of control element

Toggle

Degree of protection (IP)

IP20

Complete device with protection unit

Yes


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA075478R1 | XT4N 250 Ekip LSIG In=40A 3p F F UL/CSA

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Rated permanent current Iu

250A

Overload release current setting

16.0 .. 40A

Adjustment range short-term delayed short-circuit release

40 .. 400A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

25kA

Integrated earth fault protection

Adjustment range undelayed short-circuit release

40 .. 400A

Device construction

Built-in device fixed built-in technique

Rated voltage

240 .. 600V

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

With under voltage release

Number of poles

3

Position of connection for main current circuit

Front side

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Motor drive optional

Type of control element

Toggle

Degree of protection (IP)

IP20

Complete device with protection unit

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

We use cookies to enhance your experience.