- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- GEWISS
Technical specifications
Rated permanent current Iu
1250A
Device construction
Built-in device fixed built-in technique
Overload release current setting
500 - 1250A
Integrated earth fault protection
No
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Rated voltage
690 - 690V
Type of control element
Rocker lever
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
No
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Yes
Degree of protection (IP)
IP20
Number of auxiliary contacts as change-over contact
0
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
500 - 1250A
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Position of connection for main current circuit
Front side
Motor drive integrated
No
From same serie
MV53734

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- GEWISS
Technical specifications
Rated permanent current Iu
1250A
Device construction
Built-in device fixed built-in technique
Overload release current setting
500 .. 1250A
Integrated earth fault protection
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Rated voltage
690 .. 690V
Type of control element
Rocker lever
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Degree of protection (IP)
IP20
Number of auxiliary contacts as change-over contact
0
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
500 .. 1250A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Position of connection for main current circuit
Front side
Motor drive integrated
From same serie