Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Rated voltage

400V

Rated insulation voltage Ui

500V

Number of poles (total)

4

Rated impulse withstand voltage Uimp

4kV

Built-in depth

72mm

Number of protected poles

4

Rated current

40A

Frequency

50 - 60Hz

Current limiting class

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Power loss

14.92W

Voltage type

AC

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

12.5kA

Release characteristic

C

Over voltage category

3

Pollution degree

3

Flush-mounted installation

No

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Connectable conductor cross section multi-wired

35 - 35mm²

Additional equipment possible

Yes

Explosion-proof

No

Connectable conductor cross section solid-core

35 - 35mm²

Ambient temperature during operating

-25 - 60°C

Degree of protection (IP)

IP20

Width in number of modular spacings

4

Concurrently switching neutral conductor

No

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

GW92691

Main Product Image

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Rated voltage

400V

Rated insulation voltage Ui

500V

Number of poles (total)

4

Rated impulse withstand voltage Uimp

4kV

Built-in depth

72mm

Number of protected poles

4

Rated current

40A

Frequency

50 .. 60Hz

Current limiting class

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Power loss

14.92W

Voltage type

AC

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

12.5kA

Release characteristic

C

Over voltage category

3

Pollution degree

3

Flush-mounted installation

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Connectable conductor cross section multi-wired

35 .. 35mm²

Additional equipment possible

Explosion-proof

Connectable conductor cross section solid-core

35 .. 35mm²

Ambient temperature during operating

-25 .. 60°C

Degree of protection (IP)

IP20

Width in number of modular spacings

4

Concurrently switching neutral conductor

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.