Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Type of electrical connection of main circuit
Other
Overload release current setting
252 - 630A
Adjustment range short-term delayed short-circuit release
1.5 - 7A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Rated voltage
690 - 690V
With switched-off indicator
No
Integrated earth fault protection
Yes
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Rocker lever
With integrated under voltage release
No
Motor drive integrated
No
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1260 - 10080A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
NZMS3-4-VX630-T-AVE

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Type of electrical connection of main circuit
Other
Overload release current setting
252 .. 630A
Adjustment range short-term delayed short-circuit release
1.5 .. 7A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Rated voltage
690 .. 690V
With switched-off indicator
Integrated earth fault protection
Complete device with protection unit
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Type of control element
Rocker lever
With integrated under voltage release
Motor drive integrated
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Motor drive optional
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1260 .. 10080A