Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
400A
Overload release current setting
160 - 400A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
2 - 10A
Adjustment range undelayed short-circuit release
2 - 12A
Number of auxiliary contacts as change-over contact
0
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
Number of poles
3
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Screw connection
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Rocker lever
With integrated under voltage release
No
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Motor drive integrated
No
From same serie
NZMH3-PX400

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
400A
Overload release current setting
160 .. 400A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
2 .. 10A
Adjustment range undelayed short-circuit release
2 .. 12A
Number of auxiliary contacts as change-over contact
0
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of poles
3
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Screw connection
Suitable for DIN rail (top hat rail) mounting
Type of control element
Rocker lever
With integrated under voltage release
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Motor drive integrated
From same serie