Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
2 - 800A
Rated permanent current Iu
630A
Overload release current setting
252 - 630A
Rated voltage
690 - 690V
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
0 - 0A
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
No
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Motor drive integrated
No
Type of control element
Rocker lever
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Other
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
NZMH3-4-AX630-AVE

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
2 .. 800A
Rated permanent current Iu
630A
Overload release current setting
252 .. 630A
Rated voltage
690 .. 690V
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
0 .. 0A
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Motor drive integrated
Type of control element
Rocker lever
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Other
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
From same serie