Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
100A
Overload release current setting
40 - 100A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
2 - 10A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
2 - 18A
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Yes
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
No
Complete device with protection unit
Yes
With integrated under voltage release
No
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
Type of control element
Rocker lever
From same serie
NZMH2-PX100-TZ

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
100A
Overload release current setting
40 .. 100A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
2 .. 10A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
2 .. 18A
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Complete device with protection unit
With integrated under voltage release
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP20
Type of control element
Rocker lever
From same serie