Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Overload release current setting
640.0 - 1600A
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
No
Number of poles
4
With integrated under voltage release
No
Motor drive optional
Yes
Type of control element
Toggle
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
DIN rail (top hat rail) mounting optional
Yes
Motor drive integrated
No
Position of connection for main current circuit
Front side
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA101813R1 | XT7L M 1600 EkipG Hi-TouchLSIG 1

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Overload release current setting
640.0 .. 1600A
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
220 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Number of poles
4
With integrated under voltage release
Motor drive optional
Type of control element
Toggle
Complete device with protection unit
Degree of protection (IP)
IP20
DIN rail (top hat rail) mounting optional
Motor drive integrated
Position of connection for main current circuit
Front side
From same serie