Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as change-over contact
0
Rated voltage
220 - 690V
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
DIN rail (top hat rail) mounting optional
Yes
Degree of protection (IP)
IP20
Overload release current setting
320.0 - 800A
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
Motor drive integrated
No
With switched-off indicator
No
Motor drive optional
Yes
With integrated under voltage release
No
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
Number of poles
4
Integrated earth fault protection
Yes
From same serie
1SDA101798R1 | XT7L M 800 Ekip Hi-Touch LSIG In800 4pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as change-over contact
0
Rated voltage
220 .. 690V
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
DIN rail (top hat rail) mounting optional
Degree of protection (IP)
IP20
Overload release current setting
320.0 .. 800A
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
Motor drive integrated
With switched-off indicator
Motor drive optional
With integrated under voltage release
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Number of poles
4
Integrated earth fault protection
From same serie