Technical specifications

Rated permanent current Iu

800A

Rated voltage

220 - 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Overload release current setting

320.0 - 800A

Adjustment range undelayed short-circuit release

1200.0 - 12000A

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Yes

Adjustment range short-term delayed short-circuit release

480.0 - 8000A

Number of auxiliary contacts as change-over contact

0

With switched-off indicator

No

Integrated earth fault protection

Yes

Type of electrical connection of main circuit

Bolt connection

Number of poles

4

Complete device with protection unit

Yes

Position of connection for main current circuit

Front side

With integrated under voltage release

No

Motor drive integrated

No

Motor drive optional

Yes

Degree of protection (IP)

IP20

Type of control element

Toggle


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA101790R1 | XT7L M 800 Ekip Touch Meas.LSIG 800 4pFF

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

Rated voltage

220 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Overload release current setting

320.0 .. 800A

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Number of auxiliary contacts as change-over contact

0

With switched-off indicator

Integrated earth fault protection

Type of electrical connection of main circuit

Bolt connection

Number of poles

4

Complete device with protection unit

Position of connection for main current circuit

Front side

With integrated under voltage release

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP20

Type of control element

Toggle