Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
220 - 690V
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
With integrated under voltage release
No
Number of poles
4
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
No
Type of control element
Toggle
Motor drive integrated
No
From same serie
1SDA101686R1 | XT7S M 800 Ekip Hi-Touch LSIG In800 4pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
220 .. 690V
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
With integrated under voltage release
Number of poles
4
Motor drive optional
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Type of control element
Toggle
Motor drive integrated