Technical specifications
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Rated voltage
220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
With integrated under voltage release
No
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
With switched-off indicator
No
Number of auxiliary contacts as change-over contact
0
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
No
Rated permanent current Iu
1600A
From same serie
1SDA101393R1 | XT7S M 1600 EkipTouchMeas.LSIG 1600 3pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated voltage
220 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
With integrated under voltage release
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Motor drive optional
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Complete device with protection unit
Degree of protection (IP)
IP20
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
Rated permanent current Iu
1600A