Technical specifications
Rated permanent current Iu
800A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1200.0 - 12000A
DIN rail (top hat rail) mounting optional
Yes
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
320.0 - 800A
Integrated earth fault protection
Yes
With integrated under voltage release
No
Complete device with protection unit
Yes
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Motor drive optional
Yes
Rated voltage
220 - 690V
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
No
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Toggle
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
From same serie
1SDA101390R1 | XT7S M 800 Ekip Touch Meas.LSIG 800 3pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
320.0 .. 800A
Integrated earth fault protection
With integrated under voltage release
Complete device with protection unit
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Motor drive optional
Rated voltage
220 .. 690V
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
Type of control element
Toggle
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA