Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Overload release current setting
640.0 - 1600A
Rated permanent current Iu
1600A
Rated voltage
220 - 690V
DIN rail (top hat rail) mounting optional
Yes
With switched-off indicator
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Integrated earth fault protection
Yes
Complete device with protection unit
Yes
With integrated under voltage release
No
Motor drive integrated
No
Position of connection for main current circuit
Front side
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP20
Motor drive optional
Yes
From same serie
1SDA101385R1 | XT7S M 1600 Ekip Touch LSIG In1600 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Overload release current setting
640.0 .. 1600A
Rated permanent current Iu
1600A
Rated voltage
220 .. 690V
DIN rail (top hat rail) mounting optional
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Integrated earth fault protection
Complete device with protection unit
With integrated under voltage release
Motor drive integrated
Position of connection for main current circuit
Front side
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP20
Motor drive optional