

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Overload release current setting
400.0 - 1000A
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
Rated voltage
220 - 690V
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
No
With integrated under voltage release
No
Number of poles
3
Position of connection for main current circuit
Front side
Rated permanent current Iu
1000A
Type of control element
Toggle
Motor drive integrated
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA101379R1 | XT7S M 1000 Ekip Touch LSI In100

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Overload release current setting
400.0 .. 1000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Rated voltage
220 .. 690V
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
With integrated under voltage release
Number of poles
3
Position of connection for main current circuit
Front side
Rated permanent current Iu
1000A
Type of control element
Toggle
Motor drive integrated
Complete device with protection unit
Degree of protection (IP)
IP20
Motor drive optional
From same serie
We use cookies to enhance your experience.