Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Motor drive integrated
No
Type of control element
Toggle
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Yes
Integrated earth fault protection
No
With integrated under voltage release
No
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Number of auxiliary contacts as normally open contact
0
Number of poles
3
With switched-off indicator
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA100841R1 | XT7S 1600 Ekip Touch LSI In=1600

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
220 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Complete device with protection unit
Motor drive integrated
Type of control element
Toggle
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
With integrated under voltage release
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Number of auxiliary contacts as normally open contact
0
Number of poles
3
With switched-off indicator
From same serie