Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
800 - 8000A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
No
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
800 - 8000A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Rated voltage
220 - 690V
With integrated under voltage release
No
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
Yes
From same serie
1SDA100826R1 | XT7S 800 Ekip Dip LS/I In=800A 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
320.0 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
800 .. 8000A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
800 .. 8000A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Rated voltage
220 .. 690V
With integrated under voltage release
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP20
Complete device with protection unit
DIN rail (top hat rail) mounting optional
From same serie