

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
100A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
2 - 18A
Device construction
Built-in device fixed built-in technique
Overload release current setting
40 - 100A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Type of electrical connection of main circuit
Screw connection
DIN rail (top hat rail) mounting optional
Yes
Adjustment range short-term delayed short-circuit release
2 - 10A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
With integrated under voltage release
No
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Type of control element
Rocker lever
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
Integrated earth fault protection
No
Position of connection for main current circuit
Front side
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
NZMS2-VX100

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
100A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
2 .. 18A
Device construction
Built-in device fixed built-in technique
Overload release current setting
40 .. 100A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Type of electrical connection of main circuit
Screw connection
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
2 .. 10A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
With integrated under voltage release
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Type of control element
Rocker lever
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP20
Complete device with protection unit
Motor drive optional
Motor drive integrated
Integrated earth fault protection
Position of connection for main current circuit
Front side
From same serie
We use cookies to enhance your experience.