Aleta.hr
Main Product Image

417372 | MPX 100H MOT PREK TM 18-26A

Code: 1779982

ManufacturerLegrand
Catalog number417332
EAN code3414970396211
Order only
Zagreb0 pcs
Zadar0 pcs

Sign in or create an account for lower prices and other benefits


WSP*
220,16 €
Neto220,16
RP275,20
pcs

Details

  • Low-voltage industrial components
  • Motor protection circuit-breaker
  • 1 KOM
  • LEGRAND

Technical specifications

Degree of protection (IP)

IP20

Width

70mm

Height

165mm

Type of control element

Turn button

Number of poles

3

Depth

171mm

Rated permanent current Iu

26A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Frame clamp

Overload release current setting

18 - 26A

Adjustment range undelayed short-circuit release

338 - 338A

Rated operation power at AC-3, 400 V

11kW

Rated operating voltage

220 - 690V

With integrated under voltage release

Yes

With integrated auxiliary switch

Yes

Rated short-circuit breaking capacity lcu at 400 V, AC

100kA

Phase failure sensitive

No

Switch off technique

Thermomagnetic

Rated operation power at AC-3, 230 V

5.5kW

With thermal protection

Yes


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

417372 | MPX 100H MOT PREK TM 18-26A

Main Product Image

Code

1779982

Catalog number

417332

Type

Motor protection circuit-breaker

Manufacturer

Legrand

Serie

-

Neto WSP:

220,16

RP:275,20
* Minimum quantity1

Total stock:

0 PCS

Zadar0 PCS
Zagreb0 PCS

Details

  • Low-voltage industrial components
  • Motor protection circuit-breaker
  • 1 KOM
  • LEGRAND

Technical specifications

Degree of protection (IP)

IP20

Width

70mm

Height

165mm

Type of control element

Turn button

Number of poles

3

Depth

171mm

Rated permanent current Iu

26A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Frame clamp

Overload release current setting

18 .. 26A

Adjustment range undelayed short-circuit release

338 .. 338A

Rated operation power at AC-3, 400 V

11kW

Rated operating voltage

220 .. 690V

With integrated under voltage release

With integrated auxiliary switch

Rated short-circuit breaking capacity lcu at 400 V, AC

100kA

Phase failure sensitive

Switch off technique

Thermomagnetic

Rated operation power at AC-3, 230 V

5.5kW

With thermal protection

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

We use cookies to enhance your experience.