- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- HAGER
Technical specifications
Overload release current setting
10 - 16A
With thermal protection
Yes
Switch off technique
Thermomagnetic
Rated operating voltage
690 - 690V
Phase failure sensitive
Yes
Power loss
6.64W
Type of electrical connection of main circuit
Screw connection
Rated operation power at AC-3, 230 V
4kW
Device construction
Built-in device fixed built-in technique
Type of control element
Turn button
With integrated under voltage release
No
Rated operation power at AC-3, 400 V
7.5kW
With integrated auxiliary switch
No
Adjustment range undelayed short-circuit release
198.4 - 297.6A
Rated permanent current Iu
16A
Rated short-circuit breaking capacity lcu at 400 V, AC
50kA
Depth
75mm
Number of poles
3
Degree of protection (IP)
IP20
Height
140mm
Width
45mm
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
MM511N

Details
- Low-voltage industrial components
- Motor protection circuit-breaker
- 1 KOM
- HAGER
Technical specifications
Overload release current setting
10 .. 16A
With thermal protection
Switch off technique
Thermomagnetic
Rated operating voltage
690 .. 690V
Phase failure sensitive
Power loss
6.64W
Type of electrical connection of main circuit
Screw connection
Rated operation power at AC-3, 230 V
4kW
Device construction
Built-in device fixed built-in technique
Type of control element
Turn button
With integrated under voltage release
Rated operation power at AC-3, 400 V
7.5kW
With integrated auxiliary switch
Adjustment range undelayed short-circuit release
198.4 .. 297.6A
Rated permanent current Iu
16A
Rated short-circuit breaking capacity lcu at 400 V, AC
50kA
Depth
75mm
Number of poles
3
Degree of protection (IP)
IP20
Height
140mm
Width
45mm