Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Voltage protection level L-N
-kV
Nominal voltage DC
-V
Voltage protection level N-PE
-kV
Max. PV-voltage
-V
System configuration DC
No
Nominal discharge surge current (8/20)
15kA
System configuration other
No
System configuration TN-S
No
System configuration TN
No
System configuration TT
No
System configuration TN-C-S
No
Max. discharge surge current (8/20)
40kA
Number of conductors (without earthing)
3
System configuration TN-C
No
Voltage protection level
2.2kV
Max. continuous voltage AC
460V
Max. overcurrent protection device, parallel connection (fuse)
63A
System configuration IT
Yes
Max. overcurrent protection device, series connection (fuse)
80A
Integrated backup fuse
No
Max. conductor cross section flexible (fine-strand)
16mm²
Construction size
3 modular spacing
With remote signalling contact
Yes
Mounting method
DIN rail (top hat rail) 35 mm
Integrated short-circuit protection
No
Max. conductor cross section solid (solid, stranded)
25mm²
Short-circuit breaking capacity (Isccr)
50kA
Leakage-current free
No
Nominal voltage AC
415V
Degree of protection (IP)
IP20
Signalling at the device
Optic
Category type 2
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
A9L40321

Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Voltage protection level L-N
-kV
Nominal voltage DC
-V
Voltage protection level N-PE
-kV
Max. PV-voltage
-V
System configuration DC
Nominal discharge surge current (8/20)
15kA
System configuration other
System configuration TN-S
System configuration TN
System configuration TT
System configuration TN-C-S
Max. discharge surge current (8/20)
40kA
Number of conductors (without earthing)
3
System configuration TN-C
Voltage protection level
2.2kV
Max. continuous voltage AC
460V
Max. overcurrent protection device, parallel connection (fuse)
63A
System configuration IT
Max. overcurrent protection device, series connection (fuse)
80A
Integrated backup fuse
Max. conductor cross section flexible (fine-strand)
16mm²
Construction size
3 modular spacing
With remote signalling contact
Mounting method
DIN rail (top hat rail) 35 mm
Integrated short-circuit protection
Max. conductor cross section solid (solid, stranded)
25mm²
Short-circuit breaking capacity (Isccr)
50kA
Leakage-current free
Nominal voltage AC
415V
Degree of protection (IP)
IP20
Signalling at the device
Optic
Category type 2
From same serie