Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Nominal voltage DC
-V
Max. PV-voltage
-V
System configuration IT
Yes
System configuration TN-C-S
No
System configuration other
No
Max. continuous voltage AC
460V
Max. overcurrent protection device, parallel connection (fuse)
40A
Nominal discharge surge current (8/20)
5kA
System configuration DC
No
Nominal voltage AC
400V
Integrated short-circuit protection
No
Leakage-current free
No
System configuration TT
No
Short-circuit breaking capacity (Isccr)
50kA
Integrated backup fuse
No
With remote signalling contact
Yes
Signalling at the device
Optic
Max. conductor cross section flexible (fine-strand)
16mm²
Category type 2
Yes
Max. discharge surge current (8/20)
20kA
Number of conductors (without earthing)
4
Voltage protection level
1.8kV
Max. overcurrent protection device, series connection (fuse)
80A
Construction size
4 modular spacing
System configuration TN-C
No
Mounting method
DIN rail (top hat rail) 35 mm
Voltage protection level N-PE
1.8kV
Voltage protection level L-N
1.6kV
Max. conductor cross section solid (solid, stranded)
25mm²
Degree of protection (IP)
IP20
System configuration TN-S
No
System configuration TN
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
A9L20421
Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Nominal voltage DC
-V
Max. PV-voltage
-V
System configuration IT
System configuration TN-C-S
System configuration other
Max. continuous voltage AC
460V
Max. overcurrent protection device, parallel connection (fuse)
40A
Nominal discharge surge current (8/20)
5kA
System configuration DC
Nominal voltage AC
400V
Integrated short-circuit protection
Leakage-current free
System configuration TT
Short-circuit breaking capacity (Isccr)
50kA
Integrated backup fuse
With remote signalling contact
Signalling at the device
Optic
Max. conductor cross section flexible (fine-strand)
16mm²
Category type 2
Max. discharge surge current (8/20)
20kA
Number of conductors (without earthing)
4
Voltage protection level
1.8kV
Max. overcurrent protection device, series connection (fuse)
80A
Construction size
4 modular spacing
System configuration TN-C
Mounting method
DIN rail (top hat rail) 35 mm
Voltage protection level N-PE
1.8kV
Voltage protection level L-N
1.6kV
Max. conductor cross section solid (solid, stranded)
25mm²
Degree of protection (IP)
IP20
System configuration TN-S
System configuration TN
From same serie