Details
- Earthing, lightning and surge protection
- Combined arrester for power supply systems
- 1 KOM
- ABB
Technical specifications
Degree of protection (IP)
IP20
Mounting method
DIN rail (top hat rail) 35 mm
Number of poles
4
Construction size
4 modular spacing
Max. continuous voltage AC
275V
Signalling at the device
Optic
Max. continuous voltage DC
-V
Voltage protection level
1.3kV
Nominal voltage AC
230V
Voltage protection level L-N
1.2kV
Max. conductor cross section flexible (fine-strand)
25mm²
Max. conductor cross section solid (solid, stranded)
35mm²
Integrated backup fuse
No
Nominal voltage DC
-V
Voltage protection level N-PE
1.1kV
System configuration DC
No
System configuration TN
No
System configuration TN-S
Yes
System configuration IT
No
System configuration TT
Yes
System configuration TN-C
No
System configuration TN-C-S
No
System configuration other
No
Max. PV-voltage
-V
Lightning impulse current (10/350 µs)
12.5kA
Exhausting
No
Follow current extinguishing capability
-kA
Voltage protection level (DC+ - DC-)
-kV
Specific energy (W/R)
-kJ/Ohm
Voltage protection level (DC+/DC- - PE)
-kV
Remote signalling
Yes
Test class
Type 1 + 2
Energy-coordinated protection effect with regard to the terminal equipment
No
Voltage protection level L-PE
1.4kV
Voltage switching spark gap technology
No
Overcurrent protected voltage tapping
No
Max. overcurrent protection device, series connection (fuse)
-A
Max. overcurrent protection device, parallel connection (fuse)
-A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
2CTB815710R0900 | OVR T1-T2 N3 12.5-275s P TS QS

Details
- Earthing, lightning and surge protection
- Combined arrester for power supply systems
- 1 KOM
- ABB
Technical specifications
Degree of protection (IP)
IP20
Mounting method
DIN rail (top hat rail) 35 mm
Number of poles
4
Construction size
4 modular spacing
Max. continuous voltage AC
275V
Signalling at the device
Optic
Max. continuous voltage DC
-V
Voltage protection level
1.3kV
Nominal voltage AC
230V
Voltage protection level L-N
1.2kV
Max. conductor cross section flexible (fine-strand)
25mm²
Max. conductor cross section solid (solid, stranded)
35mm²
Integrated backup fuse
Nominal voltage DC
-V
Voltage protection level N-PE
1.1kV
System configuration DC
System configuration TN
System configuration TN-S
System configuration IT
System configuration TT
System configuration TN-C
System configuration TN-C-S
System configuration other
Max. PV-voltage
-V
Lightning impulse current (10/350 µs)
12.5kA
Exhausting
Follow current extinguishing capability
-kA
Voltage protection level (DC+ - DC-)
-kV
Specific energy (W/R)
-kJ/Ohm
Voltage protection level (DC+/DC- - PE)
-kV
Remote signalling
Test class
Type 1 + 2
Energy-coordinated protection effect with regard to the terminal equipment
Voltage protection level L-PE
1.4kV
Voltage switching spark gap technology
Overcurrent protected voltage tapping
Max. overcurrent protection device, series connection (fuse)
-A
Max. overcurrent protection device, parallel connection (fuse)
-A
From same serie
We use cookies to enhance your experience.