NZMH3-AE400-NA
Code: 1747209
Sign in or create an account for lower prices and other benefits
Code: 1747209
Sign in or create an account for lower prices and other benefits
Technical specifications
Rated permanent current Iu
400A
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
No
Rated voltage
690 - 690V
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Type of control element
Rocker lever
Motor drive optional
Yes
Degree of protection (IP)
IP20
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
200 - 400A
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
0 - 0A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Screw connection
Adjustment range undelayed short-circuit release
800 - 4400A
Number of poles
3
DIN rail (top hat rail) mounting optional
No
Zagreb:
0 pcs
Zadar:
0 pcs
NZMH3-AE400-NA
Code
1747209
Catalog number
269289
Type
Power circuit-breaker for trafo/generator/installation protection
Manufacturer
Eaton (Moeller)Serie
-
1.427,73 €
Total stock:
0 PCS
400A
0
690 .. 690V
Front side
0
0
Rocker lever
IP20
150kA
200 .. 400A
0 .. 0A
Built-in device fixed built-in technique
Screw connection
800 .. 4400A
3