- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation prot.
- 1 KOM
- SCHNEIDER
Technical specifications
Degree of protection (IP)
IP30
Type of control element
Rocker lever
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
100A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
225 - 250A
Type of electrical connection of main circuit
Screw connection
Motor drive integrated
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
150 - 1500A
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
With under voltage release
No
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Adjustment range short-term delayed short-circuit release
54 - 1000A
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
LV431807
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation prot.
- 1 KOM
- SCHNEIDER
Technical specifications
Degree of protection (IP)
IP30
Type of control element
Rocker lever
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
100A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
225 .. 250A
Type of electrical connection of main circuit
Screw connection
Motor drive integrated
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
150 .. 1500A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
With under voltage release
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Adjustment range short-term delayed short-circuit release
54 .. 1000A
Position of connection for main current circuit
Front side
Complete device with protection unit