Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Nominal voltage DC
-V
Max. PV-voltage
-V
System configuration DC
No
System configuration IT
No
System configuration TN-C-S
No
System configuration TN-S
No
System configuration TN
No
System configuration TN-C
Yes
System configuration TT
No
Nominal discharge surge current (8/20)
5kA
Nominal voltage AC
400V
Max. overcurrent protection device, parallel connection (fuse)
40A
Number of conductors (without earthing)
3
Short-circuit breaking capacity (Isccr)
50kA
Voltage protection level N-PE
1.4kV
Max. conductor cross section solid (solid, stranded)
25mm²
Voltage protection level L-N
1.1kV
Integrated backup fuse
No
Max. conductor cross section flexible (fine-strand)
16mm²
System configuration other
No
Signalling at the device
Optic
Leakage-current free
No
Category type 2
Yes
Construction size
3 modular spacing
Integrated short-circuit protection
No
With remote signalling contact
No
Degree of protection (IP)
IP20
Voltage protection level
1.4kV
Max. discharge surge current (8/20)
20kA
Max. continuous voltage AC
350V
Max. overcurrent protection device, series connection (fuse)
80A
Mounting method
DIN rail (top hat rail) 35 mm
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
A9L20300

Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Nominal voltage DC
-V
Max. PV-voltage
-V
System configuration DC
System configuration IT
System configuration TN-C-S
System configuration TN-S
System configuration TN
System configuration TN-C
System configuration TT
Nominal discharge surge current (8/20)
5kA
Nominal voltage AC
400V
Max. overcurrent protection device, parallel connection (fuse)
40A
Number of conductors (without earthing)
3
Short-circuit breaking capacity (Isccr)
50kA
Voltage protection level N-PE
1.4kV
Max. conductor cross section solid (solid, stranded)
25mm²
Voltage protection level L-N
1.1kV
Integrated backup fuse
Max. conductor cross section flexible (fine-strand)
16mm²
System configuration other
Signalling at the device
Optic
Leakage-current free
Category type 2
Construction size
3 modular spacing
Integrated short-circuit protection
With remote signalling contact
Degree of protection (IP)
IP20
Voltage protection level
1.4kV
Max. discharge surge current (8/20)
20kA
Max. continuous voltage AC
350V
Max. overcurrent protection device, series connection (fuse)
80A
Mounting method
DIN rail (top hat rail) 35 mm