Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Nominal voltage DC
-V
Max. PV-voltage
-V
System configuration TN-S
Yes
System configuration TN
No
System configuration DC
No
Number of conductors (without earthing)
3
System configuration TN-C-S
No
System configuration TN-C
No
System configuration TT
Yes
Max. discharge surge current (8/20)
20kA
System configuration other
No
Nominal discharge surge current (8/20)
20kA
System configuration IT
No
Voltage protection level
1.5kV
Max. continuous voltage AC
275V
Voltage protection level N-PE
1.5kV
Short-circuit breaking capacity (Isccr)
6kA
Voltage protection level L-N
1.5kV
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
5 modular spacing
Integrated short-circuit protection
Yes
Max. conductor cross section flexible (fine-strand)
16mm²
Signalling at the device
Optic
Max. conductor cross section solid (solid, stranded)
25mm²
Category type 2
Yes
Degree of protection (IP)
IP20
Leakage-current free
No
Nominal voltage AC
400V
With remote signalling contact
No
Integrated backup fuse
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
A9L16618

Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- SCHNEIDER
Technical specifications
Max. continuous voltage DC
-V
Nominal voltage DC
-V
Max. PV-voltage
-V
System configuration TN-S
System configuration TN
System configuration DC
Number of conductors (without earthing)
3
System configuration TN-C-S
System configuration TN-C
System configuration TT
Max. discharge surge current (8/20)
20kA
System configuration other
Nominal discharge surge current (8/20)
20kA
System configuration IT
Voltage protection level
1.5kV
Max. continuous voltage AC
275V
Voltage protection level N-PE
1.5kV
Short-circuit breaking capacity (Isccr)
6kA
Voltage protection level L-N
1.5kV
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
5 modular spacing
Integrated short-circuit protection
Max. conductor cross section flexible (fine-strand)
16mm²
Signalling at the device
Optic
Max. conductor cross section solid (solid, stranded)
25mm²
Category type 2
Degree of protection (IP)
IP20
Leakage-current free
Nominal voltage AC
400V
With remote signalling contact
Integrated backup fuse
From same serie