Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- SCHNEIDER
Technical specifications
Release characteristic
K
Rated voltage
400V
Rated current
10A
Rated insulation voltage Ui
500V
Rated impulse withstand voltage Uimp
6kV
Number of poles (total)
2
Built-in depth
44.5mm
Voltage type
AC/DC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
15kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
15kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
50kA
Current limiting class
3
Frequency
50 - 60Hz
Over voltage category
4
Additional equipment possible
Yes
Flush-mounted installation
No
Width in number of modular spacings
2
Explosion-proof
No
Number of protected poles
2
Connectable conductor cross section solid-core
1 - 25mm²
Ambient temperature during operating
-35 - 70°C
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
1 - 16mm²
Pollution degree
3
Concurrently switching neutral conductor
No
From same serie
A9F95210

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- SCHNEIDER
Technical specifications
Release characteristic
K
Rated voltage
400V
Rated current
10A
Rated insulation voltage Ui
500V
Rated impulse withstand voltage Uimp
6kV
Number of poles (total)
2
Built-in depth
44.5mm
Voltage type
AC/DC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
15kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
15kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
50kA
Current limiting class
3
Frequency
50 .. 60Hz
Over voltage category
4
Additional equipment possible
Flush-mounted installation
Width in number of modular spacings
2
Explosion-proof
Number of protected poles
2
Connectable conductor cross section solid-core
1 .. 25mm²
Ambient temperature during operating
-35 .. 70°C
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
1 .. 16mm²
Pollution degree
3
Concurrently switching neutral conductor
From same serie
We use cookies to enhance your experience.