Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Power loss
222W
Adjustment range undelayed short-circuit release
3200 - 24000A
Overload release current setting
640 - 1600A
Integrated earth fault protection
No
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
960 - 16000A
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Type of electrical connection of main circuit
Screw connection
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive optional
Yes
Complete device with protection unit
Yes
With switched-off indicator
Yes
Number of poles
3
With integrated under voltage release
No
Motor drive integrated
No
Degree of protection (IP)
IP40
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
33568
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Power loss
222W
Adjustment range undelayed short-circuit release
3200 .. 24000A
Overload release current setting
640 .. 1600A
Integrated earth fault protection
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
960 .. 16000A
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Type of electrical connection of main circuit
Screw connection
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive optional
Complete device with protection unit
With switched-off indicator
Number of poles
3
With integrated under voltage release
Motor drive integrated
Degree of protection (IP)
IP40
From same serie
We use cookies to enhance your experience.